Tel (03) 9720 8088 |
|
| |
 |
|
|
 |
Wall Mounted Fans | Wall Mounted Plate Axial Fans | SP Square Plate Range
SP Square Plate Range |
|
CONSTRUCTION Casings are manufactured from carbon steel hot dip galvanized after manufacture, and may be configured in 4 standard arrangements (see below).
IMPELLERS Axial fan impellers have true aerofoil section blades from Glass Reinforced Polypropylene (GRP), Glass Reinforced Nylon (GRN) or Aluminium (AL) material. Hubs are Aluminium or GRP and are usually supplied with taperlock centres for secure and simple fixing. Pitch angles are readily adjustable on-site with simple reference marks moulded into most components. All impellers are balanced after assembly.
MOTORS Standard units are supplied with 415V 3ph TE motors protected to IP55 with Class "F" insulation. Some applications allow increased rating motors to be used. Smaller motor sizes have sealed-for-life bearings. Larger motors with regreasng facilities may have lubrication lines extended to readily accessible external points for easy re-lubrication.
PERFORMANCE The performance figures below are given as a guide to the overall capacity of each size and speed combination. Please enquire for full details your specific duty requirement and for 1120 and 1250mm capacities.

DIMENSIONS & NOISE DATA Again, the details here are given as a guide only for each size and speed combination. Please enquire for full details your specific application, and for 1120 and 1250mm capacities.
|
Model |
A |
B |
C |
D |
E |
F |
Mass kg (Max) |
dB(A) Max 1440rpm |
dB(A) Max 960rpm |
dB(A) Max 720rpm |
|
SP340# |
540 |
490 |
467 |
420 |
500 |
9 |
46 |
61 |
|
|
|
SP350# |
655 |
615 |
587 |
460 |
550 |
11 |
56 |
69 |
59 |
|
|
SP356# |
725 |
675 |
647 |
480 |
600 |
11 |
68 |
71 |
62 |
|
|
SP363# |
805 |
750 |
717 |
560 |
660 |
11 |
80 |
74 |
64 |
58 |
|
SP371# |
850 |
810 |
797 |
560 |
660 |
15 |
128 |
76 |
68 |
61 |
|
SP380# |
970 |
910 |
887 |
700 |
840 |
11 |
195 |
80 |
70 |
64 |
|
SP3100# |
1170 |
1110 |
1088 |
700 |
840 |
11 |
257 |
88 |
78 |
72 |
ANCILLARIES A wide range of ancillary parts is available to assist with installation including: - Non-standard plate sizes - Wire guards for protection of open fan inlet/discharge
OPTIONS Special paint finishes Hazardous location motors (Ex"e", Ex"d", Ex"n", D.I.P.) 2 speed motors
Motor/impeller arrangement may be supplied using any of these four configurations. Please nominate at time of order or when requesting detailed dimensions.

|
|
|
|